COMbricks RS 485-IS Barrier
Previous product Next product

Combricks RS 485-IS BarrierThe COMbricks RS 485 Intrinsic Safety barrier is capable of creating segments for use in potentially explosive atmospheres. It complies with the specifications for PROFIBUS DP in IS segments and drives 31 RS 485-IS PROFIBUS DP devices. ProfiTrace and an Oscilloscope are integrated and also suitable for Intrinsic Safety.

The RS 485-IS barrier is the only available product for remotely monitoring IS segments over Ethernet from the safe zone. Because of the permanent mounting of the barrier, the user does not have to touch the installation anymore. This avoids hot permits and other paper work.

As an alternative it can also be used as a busmonitor on existing IS segments created by 3rd party barriers.

The IS barrier can be mixed on the backplane with other COMbricks modules like, the PROFIBUS PA, Fibre Optic and regular RS 485 modules.

IS Barrier Application

Product features

Electrical and Mechanical

  • 1 Bus channel
  • 31 devices/bus-loads per channel
  • 1200 m cable length (depends on baudrate)
  • 1 DB9 connector

Protocol

  • Transparent for all PROFIBUS protocols
  • 9.6 kbit/s – 1.5 Mbit/s (auto detection)
  • 2 bits delay time (12 bits in redundant mode)
  • No address required
  • Bus redundancy (selectable)

ATEX (electrical)

  • Uo = 4.2 V
  • Io = 149 mA
  • Ui ≥ 4.2 V
  • Li ≈ 0 μH
  • Ci = Negligibly small
  • Output characteristic: Linear

ATEX (compliance)

  • Ex II (2) G[Ex ia Gb] IIC
  • EN-IEC60079-0: 2009
  • EN-IEC60079-11: 2012
  • EN-IEC60079-25: 2010
  • Certification number: DEKRA 12ATEX0192
  • Compliant with the PNO RS 485-IS Installation Guidelines V1.1

Oscilloscope

  • Frequency: 192 MSamples/s
  • Resolution: 27 mV
  • Differential range: -3.49 to +3.49 V
  • Backplane
  • 4 Networks selectable with switches
  • 10 Modules (positioned in the first 10 slots)
  • 450 mA current consumption

Others

  • Operating temperature: 0 to 60 °C
  • Dimensions: 120 x 103 x 25 mm
  • Weight: 150 g

IS Barrier DTM

PRODUCT Price Order code Remarks
 RS 485-IS Barrier  Contact us 101-201410 Includes: Backplane unit

Remarks

The Barrier is intended to be installed outside the hazardous area or in an enclosure with a suitable type of protection.

A special IS DB9 PROFIBUS plug is required that contains a terminator defined in the RS 485-IS PROFIBUS Installation Guideline.

Previous product Next product